Worksheet: the multimeter
Name:Class:Date:
Material: the free multimeter simulator at examrobotic.com (examrobotic.com/en/tools/multimeter-simulator). Time: about 45 minutes.
Aim: choose the right function and socket, interpret readings on a three-phase supply and on a 24 V control circuit, and find faults by measuring section by section.
1. On the three-phase supply
- Set the selector to AC volts and measure. Write down the readings:
L1-L2: ______ V L1-N: ______ V L1-PE: ______ V N-PE: ______ V - Why is the phase-to-phase voltage √3 times the phase-to-neutral voltage?
- What would several volts between N and PE indicate?
- With the red lead in the A (amps) socket, measure between L1 and N. What happens? Why is it so dangerous with a real meter?
2. On the 24 V control circuit
- With the circuit working, measure the voltage across the K1 coil (A1-A2): ______ V. And across S0 when it is not pressed? ______ V. Why does a closed contact read almost 0 V?
- Switch the supply off and measure the coil in ohms: ______ Ω. Try continuity: does it beep? Why?
- Why should you never measure ohms or continuity on a live circuit?
3. Find the fault
Press «Surprise fault» three times. Measure each point to 0 V to find where the voltage is lost, and write down your method and the fault.
Answers (for the teacher)
- About 400 V phase to phase, about 230 V phase to neutral and phase to earth, and almost 0 V neutral to earth.
- The three phase voltages are 120° apart; the difference between two of them is √3 times each one (230 × √3 ≈ 400 V).
- A heavily loaded or unbalanced neutral, or a poor neutral connection: it needs checking.
- It is a short circuit through the meter: its fuse blows. With a real meter, if the fuse is not the right type, it can explode and cause an arc flash.
- About 24 V across the coil; almost 0 V across the closed contact, because it has no resistance and there is no voltage difference between its two sides. An open contact would show the full voltage.
- A few hundred ohms. It normally does not beep: the meter only beeps below a few tens of ohms.
- Because the meter injects its own current to measure: with the circuit live, the reading is meaningless and the meter can be damaged.