What 4–20 mA means and why it does not start at zero

4–20 mA is the most widely used signal in industrial instrumentation. A pressure, level or temperature transmitter turns what it measures into a current: 4 mA is 0 % of its range and 20 mA is 100 %. The PLC measures that current and converts it back into bar, metres or degrees.

Why current and not voltage

In a loop, the same current flows through every element in series. That is why it is not affected by the length of the cable or the resistance of the terminals, which would make a voltage signal drop. A current signal also resists the electrical noise from nearby motors and drives better.

Why it starts at 4 mA and not 0

The NAMUR NE 43 recommendation sets the limits many devices use: between 3.8 and 20.5 mA is a valid reading (even if slightly out of range), and below 3.6 mA or above 21 mA indicates a failure.

Try it

Enter your transmitter’s range and the current you measure, or the process value to find the current it should give:

value = start + (I − 4) / 16 × (end − start)

Two-wire and four-wire

A two-wire loop has a resistance limit: the supply must provide enough voltage for the transmitter plus the drop across the input and the cable. For example, with 24 V and a transmitter that needs 12 V, the maximum load is (24 − 12) / 0.02 = 600 Ω.

How to measure it

If the PLC is a Siemens S7-1200 or S7-1500, the analog card turns 4–20 mA into a number from 0 to 27648: the Siemens analog scaling calculator explains how to convert it into real units.

Typical mistakeThinking 0 mA means "value zero". In a 4–20 mA loop, 0 mA means no current is flowing: a broken wire, a loose terminal or a loop with no power.