Industrial automation glossary

60 terms used every day in control panels, PLCs, pneumatics and process control, each with its Spanish name and a link to the topic or simulator where it is explained in depth.

# A B C D E F G H I L M N O P R S T U V

#

4–20 mA signal ES: Señal 4–20 mA
Industrial analog signal: 4 mA is the bottom of the scale and 20 mA the top. Below 4 mA there is a fault, such as a broken wire. More on this →
5/2 solenoid valve ES: Electroválvula 5/2
Pneumatic valve with five ports and two positions, operated by a coil. It is the usual valve for double-acting cylinders. More on this →

A

Analog scaling ES: Escalado analógico
Converting the raw value of an analog input into real units. In Siemens, 0–27648 corresponds to the signal range (for example 4–20 mA). More on this →

B

Breaking capacity ES: Poder de corte
The highest short-circuit current a protective device can interrupt without being destroyed, for example 6 kA or 10 kA. More on this →

C

Capacitive sensor ES: Sensor capacitivo
Proximity sensor that detects almost any material, even liquids through a plastic tank. More on this →
Circuit breaker (MCB) ES: Magnetotérmico
Switch that protects cables against overload (thermal part) and short circuit (magnetic part). It is chosen by rating, curve and breaking capacity. More on this →
Cobot ES: Cobot
Collaborative robot, designed to work near people by limiting its force and speed. It does not remove the need for a risk assessment. More on this →
Coil (A1-A2) ES: Bobina (A1-A2)
Electromagnet of a contactor or relay. When A1-A2 is energised it closes its contacts. Always check its voltage: 24 V DC, 230 V AC… More on this →
Commissioning ES: Puesta en marcha
The ordered tests done before handing over a machine: dead checks, power section by section, inputs, outputs, safety functions and cycle. More on this →
Contactor ES: Contactor
Switch operated by a coil, which lets a small signal (a PLC output) switch a large load, such as a motor. More on this →
Counter (CTU, CTD) ES: Contador (CTU, CTD)
PLC block that counts rising edges of an input: CTU counts up to PV and CTD counts down to 0. More on this →

D

Dead time ES: Tiempo muerto
How long the measurement takes to start moving after a controller's output changes. The longer it is, the harder fast control becomes. More on this →
Double coil ES: Doble bobina
Programming mistake: writing the same output in two places in the program. The last write of the scan wins and the first one is useless. More on this →
Double-acting cylinder ES: Cilindro de doble efecto
Pneumatic cylinder that extends and retracts on air, with a chamber on each side of the piston. It is driven by a 5/2 valve. More on this →

E

Edge (rising or falling) ES: Flanco
The moment a signal changes: from 0 to 1 (rising edge) or from 1 to 0 (falling edge). In the PLC it lasts a single scan. More on this →
Emergency stop button ES: Seta de emergencia
Red button on a yellow background that stops the machine safely. It latches and has to be reset by hand. More on this →

F

Five safety rules ES: Cinco reglas de oro
Disconnect, lock out, verify absence of voltage, earth and short-circuit, and protect and mark. Always in that order, to work dead. More on this →
Flow control valve ES: Regulador de caudal
Adjustable restriction with a check valve that sets a cylinder's speed. The exhaust air is normally the one restricted (meter-out). More on this →

G

GRAFCET (sequential function chart) ES: GRAFCET
Standard way of drawing a sequence: steps (what is done) and transitions (the condition to move on to the next one). More on this →

H

HMI (operator panel) ES: HMI (pantalla de operador)
Screen from which the operator sees the machine's state, changes parameters and receives alarms. More on this →

I

Inductive sensor ES: Sensor inductivo
Proximity sensor that only detects metal, at a few millimetres. Very robust and the most common on machines. More on this →
Integral windup ES: Windup (saturación de la integral)
A PID's integral keeps growing with the output at its limit, and then the process overshoots badly. Anti-windup prevents it. More on this →
Interface relay ES: Relé de interfaz
Relay between the PLC output and the load: it protects the card and lets you switch other voltages. More on this →
Interlock ES: Enclavamiento
Condition that prevents two things happening at once, such as the forward and reverse contactors closing together. It can be electrical, mechanical or in the program. More on this →

L

Ladder logic (LAD) ES: KOP (esquema de contactos)
PLC programming language drawn like an electrical diagram, with contacts and coils. The most used in maintenance. More on this →
Limit switch ES: Final de carrera
Mechanical switch operated by a lever or plunger when a part reaches a position. More on this →
Lockout/tagout (LOTO) ES: Consignación
Locking a disconnected device with a personal padlock and a tag with name, date and reason, so nobody can switch it back on during the work. More on this →

M

Modbus ES: Modbus
Simple, widely used industrial protocol, over RS-485 (RTU) or Ethernet (TCP). Common with drives and meters. More on this →
Monostable and bistable valve ES: Monoestable y biestable
A monostable valve returns to rest on a spring when the signal is removed; a bistable valve has two coils and stays in the last position. More on this →
Motor protection circuit breaker (MPCB) ES: Guardamotor
Device that protects a motor against short circuits and, with an adjustable thermal part, against overloads. It is set to the nameplate current. More on this →
Multimeter ES: Multímetro
Instrument for measuring voltage, current, resistance and continuity. What matters is choosing the right function, socket and measurement category. More on this →

N

Normally closed contact (NC) ES: Contacto normalmente cerrado (NC)
Contact that is closed at rest and opens when operated. On auxiliary contacts, numbers ending in 1-2 (21-22, 61-62). Stop buttons are wired this way. More on this →
Normally open contact (NO) ES: Contacto normalmente abierto (NA)
Contact that is open at rest and closes when operated. On auxiliary contacts, numbers ending in 3-4 (13-14, 23-24). More on this →

O

OEE (overall equipment effectiveness) ES: OEE
Measure of how well a machine is used: availability × performance × quality. 85 % is considered world class. More on this →
Off-delay timer (TOF) ES: Temporizador TOF
Q turns on at once with IN and, when IN is removed, stays on for the time PT. Used, for example, to keep a fan running for a while. More on this →
On-delay timer (TON) ES: Temporizador TON
Q turns on when IN has been at 1 for the time PT. If IN is removed earlier, it resets. The most used: delays and filters. More on this →
Overload ES: Sobrecarga
A little more current than intended for some time, for example a motor under strain. It heats the cable slowly. More on this →
Overload relay ES: Relé térmico
Motor overload protection. Its 95-96 contact opens the control circuit when it trips, and 97-98 signals it. More on this →

P

Payback period ES: Plazo de recuperación
How long an investment, such as an automation project, takes to pay for itself with what it saves. More on this →
Phase and line voltage ES: Tensión de fase y de línea
In a three-phase supply, the voltage between two phases (line) is √3 times the phase-to-neutral voltage: 400 V ≈ √3 × 230 V. More on this →
Photoelectric sensor ES: Sensor fotoeléctrico
Sensor that uses a light beam: through-beam (separate emitter and receiver), retro-reflective (with a reflector) or diffuse (light returned by the object). More on this →
PID controller ES: PID
Controller that works out its output from the error with three actions: proportional, integral and derivative. Most industrial loops are PI. More on this →
PNP and NPN (sourcing and sinking) ES: PNP y NPN
Output type of a 3-wire sensor: PNP gives +24 V when it detects and NPN connects the output to 0 V. The PLC card has to match. More on this →
Power factor (cos φ) ES: Cos φ (factor de potencia)
What share of the apparent power is useful. A low power factor means more current for the same work, and it is corrected with capacitors. More on this →
Process image ES: Imagen de proceso
Copy of the inputs and outputs in the PLC's memory. The program works with that copy, which is updated at the start and end of each scan. More on this →
Process variable (PV) ES: Medida (PV)
The actual value the sensor measures in a control loop, such as the oven temperature. The controller compares it with the setpoint. More on this →
Profinet ES: Profinet
Industrial Ethernet network widely used with Siemens PLCs. Each device has a device name as well as its IP address. More on this →
Programmable logic controller (PLC) ES: Autómata programable (PLC)
Industrial computer that reads inputs (buttons, sensors), runs a program in cycles and writes outputs (contactors, valves). It is the brain of almost every machine. More on this →
Pulse timer (TP) ES: Temporizador TP
On an edge of IN, Q gives a pulse lasting PT, whatever IN does afterwards. More on this →

R

Residual current device (RCD) ES: Diferencial
Device that compares outgoing and returning current and trips if some is missing (earth leakage). The 30 mA type protects people. In North America, a GFCI. More on this →

S

Scan cycle ES: Ciclo de scan
What the PLC does over and over: read all the inputs, run the program from top to bottom and write the outputs. It takes a few milliseconds. More on this →
Seal-in (holding contact) ES: Autorretención
Contact of the contactor itself (13-14) in parallel with the start button, which keeps the coil energised when the button is released. In a PLC, the output in parallel with start. More on this →
Setpoint (SP) ES: Consigna (SP)
The value a control loop is trying to reach: 200 °C, 3 bar, 60 % level. The controller compares the measurement with it. More on this →
Short circuit ES: Cortocircuito
Two points at different voltages joined with almost no resistance. The current rises to hundreds or thousands of amps and must be interrupted in milliseconds. More on this →
Slip ES: Deslizamiento
Difference between the speed of the rotating field and the rotor of an induction motor. A 1500 rpm synchronous motor turns at, say, 1450. More on this →
Star-delta (wye-delta) starter ES: Estrella-triángulo
Starter that connects the motor in star and then changes to delta. Starting current and torque drop to a third. More on this →
Structured Text (ST, SCL) ES: SCL (texto estructurado)
PLC language similar to a computer programming language, with IF, CASE and loops. Handy for calculations and complex logic. More on this →

T

True RMS ES: True RMS
Meter that measures the RMS value correctly even when the waveform is not sinusoidal, such as at a drive output. More on this →

U

Utilization category AC-3 ES: Categoría de empleo AC-3
Contactor duty class for starting and stopping squirrel-cage motors. A contactor is chosen by its AC-3 current, not its AC-1 rating. More on this →

V

Variable frequency drive (VFD) ES: Variador de frecuencia
Device that changes the frequency and voltage fed to a motor to control its speed. Rectifier, DC bus and inverter. More on this →