Three-phase power calculator

The power of a three-phase load comes from the line-to-line voltage, the current and the power factor. Use it to find out how many kW a machine draws by measuring the amps with a clamp meter, to choose a transformer or a generator (rated in kVA), or to know how much current a heater or an oven will draw. Enter the current to get the power, or the power to get the amps.

The formulas

PowerThree-phaseSingle-phase
Active P (kW)P = √3 × V × I × PFP = V × I × PF
Apparent S (kVA)S = √3 × V × IS = V × I
Reactive Q (kVAR)Q = √3 × V × I × sin φQ = V × I × sin φ
Current I (A)I = P / (√3 × V × PF)I = P / (V × PF)

In three-phase, V is the line-to-line voltage (400 V in Europe; 480 V or 208 V in North America) and I is the current in each line. The formulas apply to balanced loads such as motors, ovens and three-phase heaters, and give the same result whether the load is connected in star (wye) or delta.

Example

A machine on a 400 V supply draws 10 A per phase with a power factor of 0.85:

And the other way round: an 11 kW resistance oven at 400 V (power factor 1, because it is a resistive load) draws 11000 / (1.732 × 400) ≈ 15.9 A per phase. On a 480 V supply the same oven would draw about 13.2 A.

kW, kVA and kVAR: what each one means

For motors, use the motor calculatorA motor’s nameplate power is what it delivers at the shaft, not what it takes from the supply: to go from kW to amps you also need its efficiency. Use the motor current calculator.
Typical mistakeUsing the line-to-neutral voltage (230 V, or 277 V on a 480 V system) in the three-phase formula with √3. For the example you would get 1.732 × 230 × 10 × 0.85 = 3.39 kW instead of 5.89 kW. With √3 you use the line-to-line voltage; with the line-to-neutral voltage, multiply by 3 instead of √3.

To understand the topic in depth: Practical electrical theory, with theory and a practice test.

More free simulators and calculators

Simulators: Multimeter · PNP and NPN sensor · Motor control circuit · PLC timer and counter · Pneumatics · PID controller · Star-delta starter · Ladder logic (LAD)

Calculators: Resistor colour code · 4–20 mA converter · Siemens analog scaling (0–27648) · Motor current · Voltage drop and cable size · Capacitor for a three-phase motor on single-phase · Power factor correction · Ohm’s law and power · OEE · Automation payback

Found it useful? Share it with your class or your team: WhatsApp · Telegram · LinkedIn · Email