Three-phase power calculator
The power of a three-phase load comes from the line-to-line voltage, the current and the power factor. Use it to find out how many kW a machine draws by measuring the amps with a clamp meter, to choose a transformer or a generator (rated in kVA), or to know how much current a heater or an oven will draw. Enter the current to get the power, or the power to get the amps.
The formulas
| Power | Three-phase | Single-phase |
|---|---|---|
| Active P (kW) | P = √3 × V × I × PF | P = V × I × PF |
| Apparent S (kVA) | S = √3 × V × I | S = V × I |
| Reactive Q (kVAR) | Q = √3 × V × I × sin φ | Q = V × I × sin φ |
| Current I (A) | I = P / (√3 × V × PF) | I = P / (V × PF) |
In three-phase, V is the line-to-line voltage (400 V in Europe; 480 V or 208 V in North America) and I is the current in each line. The formulas apply to balanced loads such as motors, ovens and three-phase heaters, and give the same result whether the load is connected in star (wye) or delta.
Example
A machine on a 400 V supply draws 10 A per phase with a power factor of 0.85:
- Apparent power: 1.732 × 400 × 10 = 6928 VA, about 6.9 kVA.
- Active power: 6.93 × 0.85 = 5.89 kW.
- Reactive power: 6.93 × 0.53 = 3.65 kVAR (the sine of φ when the cosine is 0.85).
And the other way round: an 11 kW resistance oven at 400 V (power factor 1, because it is a resistive load) draws 11000 / (1.732 × 400) ≈ 15.9 A per phase. On a 480 V supply the same oven would draw about 13.2 A.
kW, kVA and kVAR: what each one means
- Active (kW): the power turned into work or heat. It is what you pay for on the bill.
- Apparent (kVA): what cables, transformers and generators have to carry, because it depends on the total current. That is why that equipment is rated in kVA.
- Reactive (kVAR): what motors and ballasts need to build their magnetic field. It flows back and forth without doing work, but it loads the installation. It is compensated with capacitor banks.
To understand the topic in depth: Practical electrical theory, with theory and a practice test.